Abstract
The Sixnet I/O Tool Kit version 5.0.103 and below have a bug which will cause the Sixnet I/O Tool Kit to close unexpectedly when downloading or reading back from EtherTRAK-2 I/O modules with Tag Descriptions in their configuration are over 39 characters. To fix this you must keep Tag Descriptions below 40 characters.
Products
I/O Products:
E2-MIX24880-D/E2-MIX24882-D/E2-MIX20884-D/E2-8AO20M-D/E2-32AI20M-D/E2-32AI10V-D/E2-32DI24-D/E2-32DO24-D/E2-16AI20M-D/E2-16AI-8AO-D/E2-16DI24-D/E2-16DIAC-D/E2-16DO24-D/E2-16DORLY-D/E2-16ISO20M-D/E2-16ISOTC-D/E2-10RTD-D
Use Case: Loading configuration to E2 module
Required Software
Sixnet I/O Tool Kit 5.0.103 or below
Click the load button and the Tool Kit unexpectedly closes
- Select the EtherTRAK-2 to load.
- Go to Operations > Load.
- Result will be the Sixnet I/O Tool Kit closing unexpectedly.
Work around to stop unexpected closure of the Sixnet I/O Tool Kit
- Select the EtherTRAK-2 module. Go to Configure > Configure Station/Module.
- Go to the “I/O channels” section. Where the tag names are entered verify the “Tag Description” field is 39 characters or below.
-
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.