This guide will step through the process of resolving the “Invalid Entry Error”
Error Overview:
The error is caused by an invalid path in the ISaGRAF project definition. Go to IPm configuration window-->”ISaGRAF Options” on the “General” tab-->”Project Options” tab. Change the project name to point to a valid *.mdb file in an ISaGRAF workbench 5 project and this should prevent the issue from happening again.
Resolution:
To fix the project file, open it in a text editing program (preferably notepad++) and delete the duplicate “Destination Station Number” and “IP” lines in the “[ISaGRAF: <RTU name>]” section of the project file. Save the project file and reopen.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
Red Lion Technical Support
If you have any questions or trouble contact Red Lion Technical Support by clicking here or calling 1-877-432-9908.