Abstract:
This document describes calibrating the inputs of PAXDPxxx Panel Meters.
Products:
PAXDP000, PAXDP010
Use Case: PAXDP Calibration
Calibrating the unit to correct when the controller appears to be indicating incorrectly or inaccurately, even after troubleshooting with the factory.
WARNING!
Entering calibration mode may void the factory warranty.
The controller has been fully calibrated at the factory. Scaling to convert the input signal to a desired display value is performed in Configuration Module 1, Input Parameters. If the controller appears to be indicating incorrectly or inaccurately, refer to Troubleshooting before attempting to calibrate the controller.
Recalibration should only be performed if necessary and only by qualified technicians using appropriate calibration equipment.
NOTE 1: Module 1 program parameter may be changed during calibration. Entering CodE 48 will require that Input Parameters (Module 1) be verified after calibration is complete.
NOTE 2: For all calibrations, allow the controller to warm up for 30 minutes minimum and follow the manufacturer’s warm-up recommendations for the calibration source or measuring device
WARNING: Calibration of this meter requires a signal source with an accuracy of 0.01% or better and an external meter with an accuracy of 0.005% or better.
Before starting, verify that the precision signal source is connected to the correct terminals and ready. Allow a 30 minute warm-up period before calibrating the meter.
DISP and PAR can be chosen to exit the calibration mode without any changes taking place.
Perform the following procedure:
1. Use the arrow keys to display CODE 48 IN MENU 9-FCS and press PAR.
2. Choose the range to be calibrated by using the arrow keys and press PAR. (CAL NO and PAR can be chosen to exit the calibration mode without any changes taking place.) Select CAL OUT if calibrating an optional output card. Press PAR.
3. When the zero range limit appears on the display, apply the appropriate:
- Voltage ranges: dead short applied
- Current ranges: open circuit
4. Press PAR and the top range limit will appear on the display after approximately one second.
5. When the top range limit appears on the display, apply the appropriate:
- Voltage ranges: 10 Vdc
- Current ranges: 20 mA
6. Press PAR and CAL NO will appear on the display after approximately 1 second.
7. When CAL NO appears, press PAR twice.
8. If the meter is not field scaled, then the input display should match the value of the input signal.
9. Repeat the above procedure for each input range to be calibrated.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
Red Lion Technical Support
If you have any questions or trouble contact Red Lion Technical Support by clicking here or calling 1-877-432-9908.
For more information: http://www.redlion.net/support/policies-statements/warranty-statement