TNPC21 / TNIA39
Abstract:
This document includes a list of enhancements available beginning with PAX2C firmware version 1.5 and describes the conversion process for converting version 1.0x PAX2C file to a version 1.5+ file.
Products:
PAX2C
Use Case: Updating PAX2C Databases
In order to utilize the new features, the previous firmware version database files must be converted in order to use those files in a PAX2C with version 1.5 firmware. Instructions for converting a version 1.0x program file to be used in a version 1.5 PAX2C are included in this document.
Required Software:
Crimson 2.0 Build 572 or later
Required Firmware:
PAX2C Ver 1.51 or later
PAX2C Enhancements
Added in Version 1.50 Firmware
- FlexCard Support for:
- Heater Current Monitor (PX2FCA10)
- Process Input/Remote Setpoint (PX2FCA00)
- Custom multi-point linearization support for the standard Analog Output option card (PAXCDL10).
- Increased parameter viewing options: allows a parameter to be view/accessed in multiple display
- loops (Main, Parameter, and Hidden).
- Proportional Band is now entered as display units (was % input range).
NOTE: Programming modules affected by the enhancements include: process input scaling, display locks, and PID settings.
EXISTING VERSION 1.0X PAX2C APPLICATIONS
If you have an existing application and associated database file, you may continue to use the database on the new PAX2C using your current build of Crimson 2.0 or the latest Crimson 2.0 build contained on the USB flash drive. Simply download (Link, Send) the database file to the new PAX2C. In the download process, the new PAX2C will be “down-graded” to version 1.0x and configured for your application. If you use the build of Crimson 2.0 contained on the included USB flash drive, review the following change to the Band and Deviation Alarm Modes for version 1.06 PAX2C firmware, as it may affect your application.
PAX2C Version 1.06 Band/Deviation Alarm Mode
The PAX2C Band/Deviation alarm modes have been changed to provide setpoint tracking. As the setpoint is changed, the alarm trigger points will shift to provide alarming around the new setpoint. If you’ve previously set the alarm value to accomplish this, it is no longer necessary. The alarm value, however, will need to be set to zero; otherwise an alarm offset will occur. Refer to the Alarm Figures in the PAX2C manual contained on the USB flash drive.
DATABASE FILE/PAX2C FIRMWARE CONVERSION:
The easiest method to convert a 1.0x database file is to use the latest build of Crimson 2.0 to extract the database file from a version 1.0x PAX2C. The extracted database is then sent to the new PAX2C. To do this, follow the procedure below.
- Install Crimson 2.0 from the USB Flash Drive.
- Apply power to the version 1.0x PAX2C.
- Connect a USB cable from the PAX2C to a PC.
- Open Crimson 2.0, select File, New, select the “PAX2 Panel Meters/Controllers” Product Family and model “PX2C Temp/Process PID Controller w/FlexBus V1.5+”.
- Select Link, Extract, and “Yes” at the “Do you wish to convert?” prompt.
- The database settings will automatically be converted to a version 1.5 database file. Save the newly extracted file.
- Disconnect the version 1.0x PAX2C and apply power to the version 1.5 PAX2C.
- Connect the USB cable from the version 1.5 PAX2C to the PC.
- Send the converted version 1.5 database file to the new PAX2C using the Crimson 2 Link, Send operation.
- All settings should be checked.
If a version 1.0x PAX2C is not available, another conversion method is to send the existing 1.0x database file to the new PAX2C, as is. Then extract into a new version 1.5 database file, and resend to the PAX2C.
PROPORTIONAL BAND CONVERSION
Beginning with version 1.5, the Proportional Band units have been changed from % input range to display units. If keying in the Proportional Band value from a version 1.0x unit, the Proportional Band value must
be converted from % input range to display units. Note: The latest build of Crimson 2.0 will convert the values automatically when extracting the database from a version 1.0x PAX2C into a version 1.5 database.
Conversion Example:
Version 1.0x Settings:
Proportional Band = 21.4
Input Type = T
Display Scale = °C
Display Decimal = 0.0
Conversion of the version 1.0x Proportional Band value from % input range to display units, can be accomplished using the following formula:
Ver 1.5 Proportional Band = Input Range * (Ver 1.0x Proportional Band /100)
Using the Input Range Tables below, select the input type range for the applicable input type. In this example, we are using a Type T thermocouple, so the input range value would be 600 °C.
By substituting known values into the equation above, the version 1.5 proportional band can be calculated:
Ver 1.5 Proportional Band = Input Range * (Ver 1.0x Proportional Band /100)
Ver 1.5 Proportional Band = 600 * (21.4/100)
Ver 1.5 Proportional Band = 128.4 (For Display Scale = °F, multiply result by 1.8: For Display
Decimal point = 0, round result to nearest whole unit)
Input Range Tables
THERMOCOUPLE INPUT TYPE |
RANGE (IN °C) |
T |
600 |
E |
950 |
J |
960 |
K |
1450 |
R |
1768 |
S |
1768 |
B |
1670 |
N |
1500 |
C |
2315 |
RTD INPUT TYPE |
RANGE (IN °C) |
385 |
1050 |
392 |
1050 |
672 |
339 |
427 |
370 |
Current/Voltage/Resistance Input Type |
Range |
ALL |
Full Scale Input Range |
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
For more information: http://www.redlion.net/support/policies-statements/warranty-statement