Industrial Automation Tech Note 02 - TNIA02
Abstract:
This document describes two BACnet Slave drivers supported by Crimson®.
Products:
Red Lion Controls CR3000 Human Machine Interface (HMI), Data Station Plus (DSP), G3 HMI, Graphite® Controller, Graphite HMI, Modular Controller (MC), and ProducTVity Station™ (PTV)
Use Case: Configuring the BACnet Slave Drivers
The BACnet slave drivers differ from most other slave drivers used in Crimson. This document
provides step by step instructions for configuring Crimson to support basic BACnet slave
applications.
Required Software:
Crimson 2.0, 3.0, or Crimson 3.1
Required Operating System:
Microsoft Windows 2000, or above
Introduction
This Tech Note describes how to configure Crimson to support:
•BACnet MS/TP: Serial Communications (analog and binary (i.e., digital)
•BACnet UDP/IP or 802.3 (Raw): Ethernet Communications (analog and binary)
NOTE: Crimson is required and is only available to Windows 2000 or above users. Please update your version of Crimson to the latest, available online at: www.redlion.net.
BACnet MS/TP: Serial Communications
This section describes how to configure BACnet slave drivers within Crimson to support BACnet MS/TP: Serial Communications, for both analog data transfer and binary (digital) data transfer. Refer to steps1 thru 16 for configuring drivers for analog data transfer, and to steps 17 thru 26 for configuring drivers for binary data transfer.
Analog Data Transfer
1. Referring to Figure 1, go to the Navigation Pane and click on the Communications Port to be configured; RS485 Comms Port in this example.
2. Go to the Communications - RS-485 Comms Port window and under the Driver Selection heading select the Pick button, next to the Driver: field.
3. Go to the Driver Picker for Serial Port popup and under the Manufacturer heading select BACnet, and under the Driver heading select MS/TP Slave.
Figure 1.
4. Click OK.
5. Referring to Figure 2, configure the port settings to match the device with which the unit will be communicating:
a. The MAC Address: and Device ID: fields under the Configuration heading refer to the Red Lion device that is being programmed; 10 and 127, respectively, in this example.
b. The Max Instance: field is the number of each data type that can be auto-discovered on the network; 100 in this example.
c. The Object Properties settings are used to select how the exposed data items will be named during an auto discovery, as well as what extra information will be discovered. See each item’s bubble help for further information.
d. The Remote Management Password is used for the BACnet Reinitialize Device commands; both cold start and warm start are supported. The default value is "password".
Figure 2.
6. Referring to Figure 3, go to the Navigation Pane and click on the device below the desired port; DEV1 in this example.
7. Go to the Communications - RS-485 Comms Port - DEV1 popup and click Add Gateway Block.
8. Referring to Figure 4, click on the desired block; Block1 in this example
9. Click Pick, next to the Start Address: field. the Select Address for BACnet popup appears.
10. Choose the address to expose on the BACnet network; AV (for analog values) in this example
11. Select the appropriate Data Type and click OK:
a. Specify Real as Real if the source data is floating point
b. Specify Long as Long if the source data is an integer (as in this example)
Figure 4.
12. Referring to Figure 5, set the Block Size: field to the desired number of data points; 10 in this example.
13. Set the Direction: field to specify the direction of data transfer; Device to G3 in this example:
a. Specify G3 to Device for read only capability from the external device
b. Specify Device to G3 for read and write capability from the external device
NOTE: In step 13, the device options available for selection in the Direction: field must reflect the Red Lion Device actually being configured on the network.
Figure 5.
14. Go to the Start Address: field and click on the first address (AV0001 LONG in this example) and click the Pick button.
15. Referring to Figure 6, click on Data Tags in the Resource Pane.
16. Drag each desired tag from the Resource Pane to the Navigation Pane and drop it on the address with which it will be associated.
NOTE: The arrow between each BACnet address and its corresponding tag indicates data flow direction.
Binary Data Transfer
17. Referring to Figure 7, go to the Navigation Pane and click on the device below the port; DEV 1 in this example.
18. Got to the Communications - RS-485 Comms Port - DEV1 popup and under the Device Commands heading, click Add Gateway Block.
Figure 7.
19. Referring to Figure 8, go to the Navigation Pane and click on the desired block; Block 2 in this example
20. Click the Pick button next to the Start Address: field; the Select Address for BACnet popup appears.
21. Under the Data Item heading, select the address to expose on the BACnet network, BV (for binary values) in this example, and click the OK button.
Figure 8.
22. Referring to Figure 9, set the Block Size: to the desired number of data points; 5 in this example.
23. Set the Direction: field to specify the direction of data transfer; DSPSX to Device in this example:
a. Specify DSPX to Device for read only capability from the external device
b. Specify Device to DSPX for read and write capability from the external device
NOTE: In step 23, the device options available for selection in the Direction: field: must reflect the Red Lion Device actually being configured on the network.
Figure 9.
24. Click on the first address below the block.
25. Click on Data Tags in the Resource Pane.
26. Referring to Figure 10, drag each tag from the Resource Pane to the Navigation Pane and drop it on the address with which it will be associated.
NOTE: The arrow between each BACnet address and its corresponding tag indicates data flow direction.
Figure 10.
BACnet UDP/IP or 802.3 (Raw): Ethernet Communications
This section describes how to configure the BACnet slave drivers in Crimson to support BACnet UDP/IP or 802.3 (Raw): Ethernet Communications. Analog data transfer and binary data transfer options are described. Configuration steps 1 thru 5 are common to both data transfer options.
1. Referring to Figure 11, go to the Navigation Pane and click on the Protocol to be configured; Protocol 1 in this example.
2. Go to the Driver Selection heading and click the Pick button next to the Driver: field; the Driver Picker for Ethernet Port popup appears.
3. Under the Manufacturer heading select BACnet, and under the Driver: field select UDP/IP Slave or 802.3 Slave (much less common), as appropriate; UDP/IP Slave in this example.
Figure 11.
4. Click OK.
5. Referring to Figure 12, configure the device:
a. The Device ID: setting under the Configuration heading refers to the Red Lion device that is being programmed; 7000 in this example.
b. The Max Instance: setting is the number for each data type that can be auto-discovered on the network; 100 in this example.
c. The Object Properties settings are used to select how the exposed data items will be named during an auto discovery, as well as what extra information will be discovered. See each item’s bubble help for further information.
d. The Remote Management Password is used for the BACnet Reinitialize Device commands; both cold start and warm start are supported. The default value is "password".
Figure 12.
The initial setup for both analog data transfer and binary data transfer is now complete. To perform final configuration for analog data transfer, perform steps 6 thru 16. To perform final configuration for binary data transfer, perform steps 17 thru 26.
Analog Data Transfer
6. Referring to Figure 13, go to the Navigation Pane and click on the desired network device below the port; DEV1 in this example. The associated popup appears; Communications - Network - Protocol 1 - DEV1 in this example.
7. Click Add Gateway Block.
Figure 13.
8. Referring to Figure 14, click on the desired block; Block 1 in this example.
9. Under the Block Settings heading, click the Pick button next to the Start Address: field; the Select Address for BACnet UDP/IP popup appears.
10.Under the Data Item heading, choose the address to expose on the BACnet network; AV (for analog values)
in this example.
11.Set the appropriate Data Type, Long as Long in this example, and click OK.
a. Specify Real as Real if the source data is floating point
b. Specify Long as Long if the source data is an integer (used in this example)
Figure 14.
12. Referring to Figure 15, set the Block Size: field to the desired number of data points; 10 in this example.
13. Set the Direction: field to specify the direction of data transfer; Device to G3 in this example:
a. Specify G3 to Device for read only capability from the external device
b. Specify Device to G3 for read and write capability from the external device
NOTE: In step 13, the device options available for selection in the Direction: field must reflect the Red Lion Device actually being configured on the network.
Figure 15.
14. Go to the Navigation Pane and click on the first address below Block 1; AV0001.LONG in this example.
15. Go to the Resource Pane and click on Data Tags.
16. Referring to Figure 16, drag each tag from the Resource Pane to the Navigation Pane and drop it on the address with which it will be associated.
Figure 16.
NOTE: The arrow between each BACnet address and its corresponding tag indicates data flow direction.
Binary Data Transfer
17. Referring to Figure 17, go to the Navigation Pane and click on the device below the desired port; DEV1 in this example.
18. Click Add Gateway Block.
Figure 17.
19. Referring to Figure 18, go to the Navigation Pane and Click on the desired block; Block 2 in this example. The Communications - Network - Protocol 1 - DEV1 - Block 2 popup appears.
Figure 18.
20. Referring to Figure 19, click the Pick button next to the Start Address: field; the Select Address for BACnet UDP/IP popup appears.
21. Choose the address to expose on the BACnet network; BV (for binary values) in this example, and click OK.
Figure 19.
22. Referring to Figure 20, set the Block Size to the desired number of data points; 5 in this example.
23. Set the Direction field to specify the direction of data transfer; DSPSX to Device in this example:
a. DSPX to Device for read only capability from the external device
b. Device to DSPX for read and write capability from the external device
NOTE: In step 23, the device options available for selection in the Direction: field must reflect the Red Lion Device actually being configured on the network.
Figure 20.
24. Go to the Navigation Pane and click on the first address below Block 2; BV0001 in this example.
25. Go to the Resource Pane and click on Data Tags.
26. Referring to Figure 21, drag each desired tag from the Resource Pane to the Navigation Pane and drop it on the address with which it will be associated.
Figure 21.
NOTE: The arrow between each BACnet address and its corresponding tag indicates data flow direction.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.