Industrial Automation Tech Note 33 - TNIA34
Abstract:
This document provides step-by-step instructions for using the heartbeat bypass bit in Red Lion E3 I/O modules.
Products:
All Red Lion E3 I/O modules
Use Case: Using Counter Reset Bits
Disabling the heartbeat is useful when testing applications that do not have a heartbeat
Required Software:
Crimson® 3.0 / 3.1
Required Firmware:
Crimson 3.0 Build 700 or higher
Introduction
There are two primary tasks that must be completed when configuring Crimson to support the E3 I/O Heartbeat Bypass. First, the heartbeat must be enabled and configured within Crimson. Second, the heartbeat bypass must be configured. This document describes how to perform both tasks.
NOTE 1: Crimson support for the E3 I/O Heartbeat Bypass requires Crimson 3.0 or higher and is only available to Windows 2000 or above users. Please update your version of Crimson to the latest; available online at www.redlion.net.
NOTE 2: This document is not intended to provide comprehensive information on E3 I/O Heartbeat Bypass operation. The E3 I/O Modules Hardware Guide (LP0976) provides detailed E3 I/O module operational information, including configuration settings/options and a list of all digital and analog inputs/outputs. Download the latest version; available online at www.redlion.net.
Enable and Configure Heartbeat
To enable and configure Crimson to support the heartbeat, refer to Figure 1 and perform the following steps:
1. Start Crimson and click on Communications in the Navigation Pane.
2. Click on Watchdog/Heartbeat under Services in the Navigation Pane.
3. Set the Heartbeat Timeout option to Enabled.
4. Set other configuration options, as needed
Figure 1.
Configure Heartbeat Bypass via Crimson
The Heartbeat Bypass bit is a writable discrete and is part of each E3 I/O module’s Discrete Input (DI) status bit set. The Heartbeat Bypass bit’s address is DI 41 (Modbus 100041). As shown in Figure 2, a definition for each DI status bit is located on the System - I/O Channels page (accessed via the Navigation Pane: I/O Channels > I/O Channels). While exposed as a Modbus register, DI registers are read only. Therefore, they are only useful for monitoring Heartbeat Bypass status. Bypassing the Heartbeat needs to be done via the E3 I/O module’s web interface or via the Crimson user interface.
Figure 2.
Configure the Heartbeat Bypass via an E3 I/O module’s web interface
1. Open a web browser (Chrome, Internet Explorer, Firefox, etc…).
2. Enter the E3 I/O module’s IP address in the address bar and press Enter.
NOTE: The E3 I/O module’s default IP address, as shipped from the factory, is: 192.168.1.21
3. Navigate to the Full Access Watch Window tool by clicking Tools > Watch Window > Full Access.
4. Enable Refresh page every 3 seconds.
5. Referring to Figure 3, scroll down to DI 41 and specify the desired option:
a. Checked: Heartbeat Bypassed.
b. Unchecked: Heartbeat Honored.
6. Set other configuration options, as needed.
Figure 3.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.