IAMA / IRMA3035 / ITMA3035
Previous Models
IAMA3535 IRMA3035 ITMA3035 IAMA0006
New Model
IAMA0001
Differences
- Previous setup with dipswitches and/or applied/calibrate. Now with PGMMOD01
- Now must purchase at least one PGMMOD01 which includes a PGMMOD00
- Previous input voltage ranges lowest 0-20mV highest 0-100V. Now low 0-1V high 0-10V
- Previous input current ranges lowest 0-1mA highest 0-100mA. Now 0-20mA or 4-20mA
- Previous output voltage ranges lowest 0-5V highest 0-10V. Now low 0-1V high 0-10V
- Previous output current ranges lowest 0-1mA highest 0-20mA. Now 0-20mA or 4-20mA
- Previous field applied scaling option. Now field applied is in ADV mode CAL.
- Previous square root input model. Now no square root.
- Previous output load current 600-ohm voltage 1K-ohm. Now 600-ohm voltage 10Kohm
- Previous 22.5mm wide. Now 6mm wide.
- Previous power 9 to 32vdc. Now 16.8 to 31.2vdc
- Previous part # depends on the input. Now one part accepts all temp, analog and pot inputs.
- Previous no sensor power. Now 2.5 to 15vdc
- Previous response time 300 msec. Now 400 msec
- Previous accuracy +/-0.075% range +0.1C analog in +/- 0.1% of span. Now +/-0.1% of span
- Previous operating temp -20C to 65C. Now -25C to 70C
- Previous 12-bit resolution. Now 16-bit resolution
IAMS
Previous Model
IAMS0001
New Model
IAMS0002
Previous Model
IAMS0010
New Model
IAMS0020
Previous Model
IAMS0011
New Model
IAMS0022
Differences
- New units have different firmware, they are not interchangeable
- PGMM0D00 programming module will work with both.
- Previous no comms. Now will work with PGMMODC1 Modbus.
- Same form fit and function.
IRMA2003
Previous Model
IRMA2003
New Model
IRMA001
Differences
- Previous Type PT100 385 or 392 3 wire. Now Type any PT100 up to 4 wire
- Previous setup with calibrator. Now setup with dipswitches in 5 degrees steps.
- Previous max 790C. Now 1372C.
- Previous loop power 12 to 42vdc. Now 5.5 to 35vdc.
- Previous 22.5mm wide Now 6mm wide.
- Previous response time 400 msec. Now selectable 30ms or 300ms
- Previous accuracy +/-0.075% range +0.1C. Now RTD<0.10C TC<0.5C
- Previous operating temp -25C to 75C. Now -25C to 70C
- Previous 12-bit resolution. Now 18-bit resolution
ITMA2003
Previous Model
ITMA2003
New Model
ITMA001
Differences
- Previous Type J K T E mV. Now Type J K and RTD
- Previous setup with calibrator. Now setup with dipswitches in 5 degrees steps.
- Previous max 790C. Now 1372C.
- Previous 22.5mm wide Now 6mm wide.
- Previous response time 400 msec. Now selectable 30ms or 300ms
- Previous accuracy +/-0.075% range +0.25C. Now RTD<0.10C TC<0.5C
- Previous operating temp -25C to 75C. Now -25C to 70C
- Previous 12-bit resolution. Now 18-bit resolution
AFCM0000
Previous Model
AFCM0000
New Model
AFCM0001
Differences
- Previous power 19.2 to 30vdc. Now 16.8 to 31.2vdc and 24-240VAC
- Previous setup with dipswitches. Now programmed or using the applied method.
- Previous no comms. Now will work with PGMMODC1 Modbus.
- Previous PWM output. Now no PWM.
- Previous TTL output no. Now yes.
- Previous PNP output possible. Now yes.
- Previous voltage and ranges are the same as now.
- Previous temp, pot and resistance input no. Now yes.
- Previous voltage for output yes. Now yes.
- Previous voltage for input yes. Now 16v.
- Previous 6mm wide Now 6mm wide.
- Previous response time 1 sec. Now programmable 1-60 sec.
- Previous output up to 10khz. Now 25khz.
- Previous accuracy +/_01% Now +/_01% of span
- Previous operating temp -20C to 65C. Now -25C to 70C
- Previous no display. Now display.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
Red Lion Technical Support
If you have any questions or trouble contact Red Lion Technical Support by clicking here or calling 1-877-432-9908.
For more information: http://www.redlion.net/support/policies-statements/warranty-statement