PLEAE NOTE
The rear input terminals are the same on all three DIN size PXU series controls.
Note the PXU series process control can support 2,3, and 4 wire PT100 RTDs.
APPLICABLE PRODUCTS
All PXU series process controls
PRE-REQUISITES
- PT100 RTD 4 wire
IN THIS ARTICLE
- Wiring procedure to install a 4 wire PT 100 RTD
The purpose of this article is to explain the proper wiring of a PT100 4 wire RTD to a PXU series process control.
For the purposes of this example, the PXU 1/16TH DIN unit will be discussed paired with a PT100 RTD with the below color combination. However, any PXU series DIN size will be similar.
PXU 1/16TH DIN rear terminals
PT100 4 wire RTD
Depending on the brand of your RTD the color code may vary but the wiring principle is the same.
Wiring:
PXU terminal 10 BLK (R4 and R3)
PXU terminal 11 RED (R2)
PXU terminal 12 RED (R1)
ADDITIONAL INFO
LINK to PXU Product Manual